VISION FRAMES

INSTALLATION INSTRUCTIONS
VANCOUVER DOOR WH 20 MINUTE WOOD VISION FRAMES
NEUTRAL PRESSURE

1.  Prior to the installation, position the glazing clips on 1/4" wire glass at 6" maximum from each corner on all the vertical and horizontal edges. Then place additional clips as needed at 12" maximum from each corner clip, a minimum of two clips per side. Position WHI label tag on bottom edge centered.

2.  Set wire glass with clips and label tag applied, in the door cut out and nail with the clips with 1-1/4" common nail on each side of clip, using holes in clip.

3.  Apply Glazing tape or caulking compound approved for fire stopping sealant to the premitered wood moulding.

4.  The wood moulding can now be set in place and nailed with 1-12" finish nails 8" on center, with a minimum of 2 nails per piece.